User Guide
Chapter 11 - System Configuration
Initial Value Editor
174
Siemens Industry, Inc.
BACnet Field Panel Web Server User Guide
125-3584
2017-07-31
Using the Initial Value Editor
Setting the Initial Value
1. Click the Initial Value icon from the System Configuration bar.
The Initial Value Editor window displays.
2. Select the desired panel by double-clicking the panel name or by clicking the arrow
next to the name of the desired panel in the left pane of the Initial Value Editor
window.
3. Select the desired device by clicking the arrow next to the name of the desired FLN
and then clicking the name of the desired device.
The Points table displays.
4. Set the initial value by using the cells under the Initial Value column in the Points
table.
5. Click Save.
The Save button becomes grayed out once the modifications are complete.
Updating the Panel
NOTE:
The Update Panel functionality is not supported on DXR devices.
1. Click the Initial Value icon from the System Configuration bar.
The Initial Value Editor window displays.
2. Select the desired panel by double-clicking the panel name or by clicking the arrow
next to the name of the desired panel in the left pane of the Initial Value Editor
window.
3. Select the desired device by clicking the arrow next to the name of the desired FLN
and then clicking the name of the desired device.
The
Points table displays.
4. Update the panel by clicking the Update Panel button.
The Initial Value column is automatically filled in with values read from the
device.