User Guide

Chapter 11 - System Configuration
Initial Value Editor
173
Siemens Industry, Inc.
BACnet Field Panel Web Server User Guide
125-3584
2017-07-31
The Initial Value feature requires the correct case-sensitive password for MS/TP
device re-initialization. The password for MS/TP device re-initialization is configured
when adding/modifying an MS/TP FLN device to the field panel.
User Interface Description for the Initial Value Editor
The
Update Panel button allows you to update the panel with the initial values.
The
Initialize Device button allows you to initialize the selected device by
commissioning the values set.
The
Points table lists the points that exist in the selected FLN device. The table
lists the following point information:
Point Name displays the name of the point.
Object ID displays the Object Identifier.
Initial Value allows you to set or modify the initial value of the point.
Release check box allows you to release the selected point, returning the
initial values to their relinquished default values.