User Guide

Chapter 11 - System Configuration
Initial Value Editor
172
BACnet Field Panel Web Server User Guide
125-3584
2017-07-31
Deleting an FLN Device
1. Click the FLN icon from the System Configuration
bar.
The
FLN Editor window displays.
2. Select the desired panel and FLN by clicking the arrow next to the panel name and
then the arrow next to the FLN name.
3. Select the desired FLN device by clicking the FLN device name.
The appropriate
Device Editor window displays the FLN device details.
4. Click the minus button at the bottom left of the FLN Device Editor window.
A message box displays, allowing you to verify deletion of the selected FLN
Device.
5. Click Yes to delete the selected device.
Initial Value Editor
The Initial Value Editor allows you to load initial values into a Siemens (or other third-
party) device that uses P1 or BACnet MS/TP communication, through the BACnet
Field Panel Web Server user interface, if necessary.
The Initial Value Editor allows you to:
Save the current initial values of a device into the field panel using the
Update
Panel button.
Load initial values into a device using the
Initialize Device button.
Set new values or release existing values using the
Save button.
Accessing the Initial Value Editor
To access the
Initial Value Editor, move your cursor over the FLN icon in the
System Configuration bar on the left side of the
screen, and then click the
Initial Value icon:
About Initial Values
The purpose of initial values is to provide a starting value for an FLN device in case
power is cycled. If the device is connected to a BACnet field panel, these values are
retained and sent to the device. If a device becomes damaged, the new device can be
addressed, and its application set, and the field panel will send the initial values so the
device is configured correctly.
The Initialize Device feature allows you to load initial values to a device if necessary.
Also, Individual points can be released through the Initial Value Editor.