User Guide
Chapter 11 - System Configuration
FLN Editor
168
Siemens Industry, Inc.
BACnet Field Panel Web Server User Guide
125-3584
2017-07-31
Using the FLN Device Editor
Adding an FLN Device
In addition to the default FLNs displayed, MS/TP Routed and Integration FLNs may be
added if the field panel has been enabled for MS/TP FLN and has Firmware Revision
3.4. A routed FLN allows the field panel to supervise FLN devices on the MS/TP side
of an IP-to-MS/TP router.
The field panel's FLN configuration determines the default FLNs displayed for a panel.
For more information, see the
Panel Configuration Editor
[➙ 209] section.
Figure 4: Adding a Routed FLN to the Field Panel.
1. In the FLN Editor, select a field panel with Firmware Revision 3.4 or later.
2. Click the Add FLN button at the bottom of the pane.
A dialog box opens.
3. Enter the FLN number associated with the network to be accessed.
4. Click the Add button.
Creating an FLN Device
If you’re adding a device to the primary or secondary FLN, you must know the
MS/TP FLN Network Number. To determine this, navigate to the
Panel
Configuration Editor, click the FLN Settings tab, and note the numbers for the
Primary and Secondary FLNs. To determine which physical port is primary and
which is secondary, see the Using the
Panel Configuration Editor
[➙ 214] section.
1. In the FLN Editor, select a field panel in the device tree to display available FLNs.
2. Select the desired FLN.