User Guide

Chapter 11 - System Configuration
FLN Editor
167
Siemens Industry, Inc.
BACnet Field Panel Web Server User Guide
125-3584
2017-07-31
9
Click the Export to CSV button to export the displayed table data to a Comma Separated Variable (.csv)
file, which can be saved.
10
The data in the following columns is read directly from the discovered device(s):
Instance # - The device identification number. This field cannot be modified.
Name - The device name. This field is required, and it cannot be modified once the device has been
added to the database. Up to 30 alphanumeric characters are allowed. The following characters are
not allowed:
* : ? [ ] #
MAC Address - The MAC address of the device. This field cannot be modified.
Application # - The device application number. When using the Device Discovery table, this field is
required in order for the field panel to learn the application. This field cannot be modified after the
device is added to the database.
If the device is a PPM or third-party device, the valid Application number range is 1000011999.
If the device is a UEC, panel, PTEC, or BTEC, the valid Application number range is 1-32767, or
the field can be left blank. If left blank, the field panel will query the device for the application
number.
Type - The device type (BTEC, PTEC, MSTP, PPM, UEC, PANEL, DXRE, or DXRM). This information
cannot be modified.
Description - The device description. This field is optional and can be edited. Up to 16 alphanumeric
characters are allowed. The following characters are not allowed:
“ * : ? [ ]
Password - Allows you to choose a password for the device, using up to 20 alphanumeric characters.
For a UEC or field panel, this field is required in order to use the Point Editing, PPCL Editing, and
Database Management features of the BACnet Field Panel Web Server. If the device is a
UEC/PANEL, enter the password for the HIGH user account that is stored in the UEC/PANEL device
database in all uppercase.
11
Click the Restart Discovery button to manually trigger a device discovery process. This button is only
available when the discovery process status is complete.