User Guide

Chapter 11 - System Configuration
FLN Editor
164
BACnet Field Panel Web Server User Guide
125-3584
2017-07-31
8
Initial Value Priority - Allows you to provide the priority used for writing initial
values. The default value is 15.
9
The Save Relinquish Default Value options (Y/N) - Allows you to specify
whether or not the relinquish default values of the device will be stored in the
field panel.
10
Device Password - Allows you to choose a password for the device, using up to
20 alphanumeric characters.
If the FLN device is a UEC/PANEL:
This field is required in order to use the Point Editing, PPCL Editing, and
Database Management features of UI Revision 1.3.
x
.
Enter the password for the
HIGH user account that is stored in the
UEC/PANEL device database in all uppercase. Use Commissioning Tool
(CT)/HMI to set the HIGH user account password in the UEC/PANEL FLN
device database.
P1 Device and Integration Device Editor Windows
The following figure outlines the device editor user interface for both P1 devices and
Integration devices.
When a P1 device is selected from the FLN Editor device tree, the
P1 Device
Editor pane displays.
When an Integration FLN device is selected from the FLN Editor tree, the
Integration Device Editor pane displays.
1
Object Name - The name of the FLN Device. This field cannot be modified
once the device has been added to the database. Up to 30 alphanumeric
characters are allowed. The following characters are not allowed:
* : ? [ ] #
2
(
Optional
) Description - The device description. This field can be edited. Up to
16 alphanumeric characters are allowed. The following characters are not
allowed:
“ * : ? [ ]
3
Address - Allows you to enter the FLN Number and Drop Number. This field
cannot be modified once the device has been added to the database
4
Application Number - Allows you to specify the application number.
5
Instance # - Allows you to enter a device identification number. This field
cannot be edited in an existing object.