User Guide
Chapter 11 - System Configuration
FLN Editor
163
Siemens Industry, Inc.
BACnet Field Panel Web Server User Guide
125-3584
2017-07-31
4
1
2
5
3
6
7
8
9
10
1
Object Name - The name of the FLN Device. This field cannot be modified
once the device has been added to the database. Up to 30 alphanumeric
characters are allowed. The following characters are not allowed:
* : ? [ ] #
2
(
Optional
) Description - The device description. This field can be edited. Up to
16 alphanumeric characters are allowed. The following characters are not
allowed:
“ * : ? [ ]
3
Application Number - allows you to specify the application number.
● If the device is a PPM or third-party device, the valid range for the
Application Number field, in order for the field panel to learn the MS/TP
application, is 10000 through 11999.
● If the device is a UEC, PANEL, PTEC, or BTEC, the valid range for the
Application Number field is 1 through 32767, or the field can be left blank. If
left blank, the panel will query the device for the Application Number.
4
The Master/Slave options allow you to select the type of device being created.
This field can be modified.
NOTE: IP devices can only be Master devices and do not have this field.
● When an MS/TP device is added as a Master device, either the
Instance #
or the
MAC Address must be specified. After a Master device is added to
the database, the
Network # and the MAC Address cannot be modified
● When a device is added as a Slave device both the
Instance # and the
MAC Address must be specified. After a Slave device is added to the
database, the
Network # and the MAC Address can be modified.
5
Instance # - Allows you to enter a device identification number. This field
cannot be edited in an existing object.
● If the FLN Device is a Master device, and you do not enter a value, the
controller automatically enters the next available Object ID.
● If the FLN Device is a Slave device, then the pre-assigned Object ID must
be provided.
6
Network Number - Allows you to enter the selected FLN network number of the
selected field panel. If no value is provided, the controller uses the network
number from the database.
7
MAC Address - Allows you to enter the MAC address. This field
can
be
modified in the MS/TP Device Editor form. This field
cannot
be modified in the
IP Device Editor form.