User Guide
Chapter 2 - BACnet Field Panel Web Server System Administration
Loading the User Interface
16
Siemens Industry, Inc.
BACnet Field Panel Web Server User Guide
125-3584
2017-07-31
Loading the User Interface
Loading or Upgrading the User Interface Using the Siemens Launch
Pad
Complete this procedure to load or upgrade the User Interface file when using the
Siemens Launch Pad (recommended method).
1. From the Tools menu in the Siemens Launch Pad tool, select Deploy Web Server
To Panel.
The Deployment dialog box displays the version of the user interface you are
about to install.
2. Enter the name or the IP address of the field panel to which you are deploying the
user interface upgrade file.
3. Enter the user name and password.
4. Select which language files to deploy.
5. Click Start.
The progress bar displays.
6. Click Close when the installation is complete.
Loading or Upgrading the User Interface Using the Human-Machine
Interface (HMI)
Complete this procedure to load or upgrade the User Interface file using the HMI.
1. Copy the UIUpgrade folder and its contents from Standard Apps/Partner Extranet
onto the root of a USB memory device (such as a thumb drive). Do not change the
folder or file structure.
NOTE:
The files within the
UIUpgrade folder include wsroot/fpweb.swf, as well as language
(.mo) files and other support files.
2. Insert the USB memory device into the USB port of the field panel.
NOTE:
Due to USB memory device manufacturer, size, and contents, the time to detect the
device will vary from several seconds to one or more minutes. You may verify that the
device is attached by using the HMI commands
S, H, F, F, L to list the available
drives on the field panel, and confirm that Drive
B is listed.