User Guide
Chapter 10 - Create/Edit
PPCL
155
Siemens Industry, Inc.
BACnet Field Panel Web Server User Guide
125-3584
2017-07-31
● Adding a PPCL program with the same name allows you to change its priority
without deleting any of the existing program. However, this action does not release
any points set at the program’s original priority.
● If a field panel must command a PTEC point, the priority of the PPCL program
must be set to 15 or higher.
● If a field panel must command a UEC point, the priority of the program
commanding it must be set higher than the priority of any UEC program that
commands the point. Not all points in the UEC will be commanded by PPCL.
List of Reserved Words for Field Panels or UEC Devices
The following keywords and statements are reserved for specific functions and
should
not
be used as or as part of point names used in a Field Panel or UEC PPCL program.
$ARG1 through $ARG15
$BATT
$LOC1 through $LOC15
$PDL
.AND.
.EQ.
.GE.
.GT.
.LE.
.LT.
.NAND.
.NE.
.OR.
.ROOT.
.XOR.
@EMER
@NONE
@OPER
@PDL
@SMOKE
ADAPTM
ADAPTS
ACT
ALARM
ALMACK
ALMCNT
ALMCT2
ALMPRI
AND
ARG1 through ARG15
ATN
AUTO
C (comment)
COM
COS
CRTIME
DAY
DAYMOD
DAYOFM
DBSWIT
DC
DCR
DEACT
DEAD
DEFINE
DISABL
DISALM
DISCOV
DPHONE
ELSE
EMAUTO
EMER
EMFAST
EMOFF
EMON
EMSET
EMSLOW
ENABLE
ENALM
ENCOV
EPHONE
EQ
EQUAL
EXP
FAILED
FAST
GE
GOSUB
GOTO
GT
HAND
HLIMIT
HOLIDA
IF
INITTO LE
LINK
LLIMIT
LOC1 through LOC15
LOCAL
LOG
LOW
LOOP
LSQ2
LSQDAT
LT
MAX
MIN
MONTH
NAND
NE
NGTMOD
NIGHT
NODE1 through NODE99
NONE
NOR
NORMAL
OFF
OIP
OK
ON
ONPWRT
OPER
OR
PDL
PDLDAT
PDLDPG
PDLMTR
PDLSET
PPCL
PRFON
RELEAS
RETURN
ROOT
SAMPLE
SECND1 through
SECND7
SECNDS
SET
SIN
SLOW
SMOKE
SQRT
SSTO
SSTOCO
STATE
TABLE
TAN
THEN
TIMAVG
TIME
TOD
TODMOD
TODSET
TOTAL
WAIT
XOR