User Guide

Chapter 10 - Create/Edit
PPCL
145
Siemens Industry, Inc.
BACnet Field Panel Web Server User Guide
125-3584
2017-07-31
NOTE:
Excessive referencing of points from other panels may cause network performance
issues.
NOTE:
Only points located in the Web client's cache (as displayed in the Device/Points list)
will display in the tree view. If the desired point is not displayed, the cache must be
refreshed by clicking the refresh arrows.
Statement Parameter Rules
If the parameter can only be a number:
You can only enter 0 through 9, -, or . (period).
If the parameter can only be a point:
You must adhere to the rules for Point Names. See the
PPCL Manual
for more
information about Point Names.
If “” or @ are required (such as a point name beginning with a number, or a point
name greater than 6 characters), the editor will automatically apply “” around the
point name.
NOTE:
You cannot enter “” in a point name, as this is a prohibited character for a point name.
However, “” can be entered around a point name.
If the parameter can be either a number or a point:
If you enter a parameter containing all numbers, or all numbers and a single
decimal point, the entry will be treated as a number.
If the parameter begins with a - and all remaining characters are 0 through 9, the
entry will be treated as a number.
If you enter “” around the parameter, the entry will be treated as a point name.
If the parameter contains any non-alphanumeric characters, the entry will be
treated as a point name and “” will be added when applicable.
Drag and Drop
The Drag and Drop feature allows you to drag points from the
Device/Points list and
drop them into a line of a PPCL program.
NOTICE
You CANNOT drag a point from the Device/Points list and drop it into a parameter of
an open command form. See the
Forms
section for more information about using
forms.
When a point is dropped into a PPCL program in an ALN Device, the System
Name will be dropped into the line of PPCL. For more information, see the
System
Name and Name
section.