User Guide
Chapter 10 - Create/Edit
Notification Class
118
Siemens Industry, Inc.
BACnet Field Panel Web Server User Guide
125-3584
2017-07-31
– Transitions – Defines which transitions are sent by the Notification Class (Off
Normal, Fault, Normal).
–
Confirmed notification – Enables confirmed notification, which means that the
notification expects an acknowledgement of receipt from the notification
recipient. Not available if broadcasts are selected for notifications.
● (
Optional
) The Remote Destinations table is a table which lists remote recipient
destinations and rules. One entry line is allotted for each destination and rule. This
table is optional for Notification Class creation and can be edited. Each destination
has the following parameters:
–
Remote Recipient – Select the remote notification e-mail address from a drop-
down list.
–
Valid Days – Select one or multiple days when the Remote Notification
Destination is valid (Mon, Tue, Wed, Thu, Fri, Sat, Sun).
–
From Time – Start time when the Remote Notification Destination is valid. This
field uses local panel time.
–
To Time – End time when the Remote Notification Destination is valid. This
field uses local panel time.
–
Transitions – Defines which transitions are sent by the Notification Class (Off
Normal, Fault, Normal).
The width and order of the table columns can be changed in the application pane, but
the changes remain only for the current session. Once you leave the editor, the column
configuration reverts to the default settings.
● To change the width of the columns, click and hold the vertical edge of the column
header and move the line to the desired width.
● To change the order of the columns, click and hold the column and move it to the
desired location within the table.
Using the Notification Class Editor
If a Remote Destination is added to a Notification Class object, all recipients in the
Remote Destinations table will receive an e-mail notification of the alarm condition.
Notification will come from the Sender’s E-mail Address field as configured in the
SMTP Configuration Editor. The e-mail notification will indicate the
time local to the
field panel
, as well as the field panel name, point system name, point descriptor, “to”
state, event value, and priority:
From: MichaelS@fwrd.rd.net [mailto:MichaelS@fwrd.rd.net]
Sent: Friday, September 09, 2011 4:29 AM
To: Smith, Michael
Subject: Building Automation Alarm Notification
Field panel name :EPXCM80
Time Stamp :09:29:17 SEP-09-2011 FRI
Point system name :mm
Point Descriptor :
To State :*A1*unACK
Event Value : 100.0
Priority :BN08