Chapter 10 - Create/Edit
Notification Class
117
Siemens Industry, Inc.
BACnet Field Panel Web Server User Guide
125-3584
2017-07-31
The
Object Name field allows you to name the Notification Class Object using up to
30 characters. This field is required for creating a Notification Class
Object and
cannot be edited in an existing object.
The
Object Identifier field displays the Object identification information. If you do
not enter a value, the controller will automatically enter the next available Object
ID. This field cannot be edited in an existing object.
(
Optional
) The Description field allows you to describe the Notification Class Object
using up to 16 characters. This field is optional for creating a Notification Class
Object creation and can be edited.
(
Optional
) The To OFFNORMAL, To FAULT, and To NORMAL Priority fields allow
you to set the notification priority for the three transition types. This parameter is
optional for Notification Class creation and can be edited.
(
Optional
) The Network Destinations table is a table which lists notification class
destinations and rules. One entry line is allotted for each destination and rule. This
table is optional for Notification Class and can be edited. Each destination has the
following parameters:
Process ID the default is 600 but it can be set to any other value.
Recipient Select one of the following:
Device Instance Integer providing the device object identifier.
Address MAC address and integer for network number.
Broadcast Select one of three: Local (Broadcast to local network only),
Remote and Network # (Broadcast to remote network), or Global (Broadcast to
all networks).
Valid Days Select one or multiple days when the Notification Class is valid
(Mon, Tue, Wed, Thu, Fri, Sat, Sun).
From Time Start time when the Notification Class is valid. This field uses local
panel time.
To Time End time when the Notification Class is valid. This field uses local
panel time.