User Guide

Chapter 10 - Create/Edit
Event Enrollment
113
Siemens Industry, Inc.
BACnet Field Panel Web Server User Guide
125-3584
2017-07-31
The Object Name field allows you to name the Event Enrollment Object using up to
30 characters. This field cannot be edited in an existing object.
The
Object Identifier field displays the point Object Identifier information. An Object
Identifier consists of an object type and instance number. The object type is the
BACnet standard object type enumeration value (Event Enrollment object type
enumeration value is 9). You can enter an instance number on point creation in this
field, or leave it blank. If you do not enter an instance number in the
Object
Identifier field when creating, the controller automatically enters the next available
instance number. After creation, the Object Identifier field cannot be edited and the
field will show the object type and instance number separated by commas.
(
Optional
) The Description field allows you to describe the Event Enrollment Object
using up to 16 alphanumeric characters. This field can be edited.
The event type options allow you to choose the Event Enrollment Object type:
COS - Change of State (for BI, BV, MI, and MV point types)
FAL - Command Failure (for BO and MO point types)
LIM - Floating Limit (for AO and AV point types)
OOR - Out of Range (for AI, AO, and AV point types)
(
Optional
) The OFFNORMAL, NORMAL, and FAULT Alarm Enabled check boxes
allow you to define which transitions will be reported. These parameters can be
edited.
The Notify Type drop-down menu allows you to choose “alarm” or “event” type of
notification.
The
Reference Point field allows you to choose the object reference for the object
to be monitored. This parameter is required for creating an Event Enrollment
Object and cannot be edited.
The
Time Delay field allows you to specify the time (in seconds) that the object
must be in or out of alarm or fault for a notification to be sent.