Installation Instructions

Document No. 545-405
Installation Instructions
Rev. 7, February, 2002
Page 2 of 4
Siemens Building Technologies, Inc.
Instructions
Each Point Module has a small piece of colored-
coded tape (Item 7 in Figure 2) affixed to the right
side of the transparent identification window to
identify the point type. Table 1 outlines PTM color-
coding.
Table 1. PTM Color-Coding.
Tape
Color
Point Type
Blue Analog Input
Yellow Analog Output
Pink Analog Output-Pneumatic
Orange Pulse Counting
Clear Digital Input
Green Digital Output
1. Match the layout sheet point module address
number (for example, 00200004) to the same
number shown on your label sheet.
Example
OR2SP 0R1SP
SUPPLY PROOF SUPPLY PROOF
00200005
00200004
NOTE:
If pre-addressed labels have not been
supplied, identify each point module by
legibly writing the following information for
each point on the paper label: Name,
Description, and Address.
2. Remove the label from the perforated sheet.
Fold label to double thickness and insert it
through the slot located on the left-hand side of
the module (Figure 3). The label should fit
snugly under the transparent module
identification window.
3. Repeat Steps 1 through 2 for each point module
being labeled.
Figure 3. Labeling the Point Module.
1. Point module
2. Termination block
NOTE:
High voltage termination blocks are dark gray.
Low voltage termination blocks are light gray.
3. Transparent module identification window
4. Point identification label
5. Status LEDs and manual override
6. Address key
7. Color-coded tape
8. PTM and M-Bus connector
9. Mechanical keys to prevent the insertion of unmatched voltages
10. Point module and termination block connector
11. Termination block screw contact
12. Termination block address marker
13. Termination block part number
PTX6.H (High voltage)
PTX6.L (Low voltage)
14. Mounting rail
15. Module Bus (M-Bus)
Figure 2. Point Termination Module Components.