Engineering Documentation

Table Of Contents
Chapter 3 Field Panels
TX-I/O Product Range
125
-3002
99 | 231
Digital Input Module Terminal Layout.
TXM1.8D, TXM1.16 D TXM1.16D only
I/O point
(1) (2) (3) (4) (5) (6) (7) (8) (9) (10) (11) (12) (13) (14) (15) (16)
System Neutral (–)
1)
1 3 5 7 9 11 13 15 18 20 22 24 26 28 30 32
Input (+)
2 4 6 8 10 12 14 16 19 21 23 25 27 29 31 33
1)
Terminals 1, 3, 5 etc. are neutral terminals. They are connected in the plug-in I/O module but not in the terminal base. When the
I/O module is removed, there is no connection.
Dry Contacts; Supervised, Digital Input Module
K1 Status contact (N/O)
K2 Status contact (N/C)
K3 Pulsed accumulator
S5 Electronic switch (rated for 30V,
10 mA)
Dry Contacts; Supervised, Digital Input Module.
Digital Output Modules (TXM1.6R and TXM1.6R-M)
DANGER
Digital Output modules connected to high voltage should incorporate a readily
accessible disconnect device outside the panel.
All low voltage and high voltage wiring must be routed separately within an enclosure so that
low voltage and high voltage wiring cannot come in contact with each other. High- and low-
voltage circuits cannot be located on adjacent terminals within a module.
TXM1.6R TXM1.6R-M