Engineering Documentation

Table Of Contents
Chapter 3 Field Panels
TX-I/O Product Range
98
| 231
125-3002
Symbols
TX-I/O modules use the following set of symbols.
System neutral (‘N’ on MEC Service Box)
Protective Earth (PE) is Approved Building Earth Ground terminal at enclosure
(output to terminal “ ” on PX Series Service Boxes or terminal ‘E’ on MEC
Service Box)
Protective Ground input on equipment for connection to PE
Equipotential (RS-485 communications common reference terminal)
Configurable point
Output (arrow pointing OUT from center of module)
Input (arrow pointing IN toward center of module)
24 Vdc output (field supply)
AC/DC output, 12 to 24V (field supply)
~
24 Vac input from Service Box (‘H’ on MEC Service Box)
Digital Input Modules (TXM1.8D and TXM1.16D)
NOTE:
Potential free (dry contact) for all points.
The neutral of a digital input can be connected to any neutral terminal on the same
module. Several digital inputs can also share a neutral terminal on the same module.
NOTE:
Counter inputs faster than 1 Hz that are routed for more than 33 ft (10 m) in the same
wire runs as analog inputs must be shielded.
TXM1.8D TXM1.16D