Engineering Documentation

Table Of Contents
Chapter 3 Field Panels
TX-I/O Product Range
125
-3002
89 | 231
Power Source Requirements
WARNING
Install external supply line fusing in series with relay contacts and controlled
device.
Fuse type and value should be lowest required by control relay datasheet or
controlled device datasheet.
Failure to install fuse may result in damage to relay or device.
TX-I/O Power Source Requirements – I/O Modules.
Product Part Number Input
Voltage
Maximum Power
1)
Digital Input Module TXM1.8D 24 Vdc 1.1 W
Digital Input Module TXM1.16D 24 Vdc 1.4 W
Relay Module TXM1.6R 24 Vdc 1.7 W
Relay Module TXM1.6R-M 24 Vdc 1.9 W
Universal Module TXM1.8U 24 Vdc 1.5 W
2
Universal Module TXM1.8U-ML 24 Vdc 1.8 W
2
Super Universal Module TXM1.8X 24 Vdc 2.2 W
2) 3)
Super Universal Module TXM1.8X-ML 24 Vdc 2.3 W
2,3
1)
The 24 Vdc self forming TX-I/O Bus and interconnecting wiring is Class 2.
2)
Class 2 Distribution Terminals are provided for 24 Vac.
3)
Class 2 Distribution Terminals are provided for 24 Vdc. A maximum of 4.8 W per module may
be distributed for external sensors. This is not included in the maximum power shown above.
PXC Series Power Source Requirements.
Product Input Voltage Maximum Power
Consumption
24 Vdc Sensor Power
Output
1)
PXC Modular 24 Vac 24 VA N/A
PXC Compact 36 24 Vac 35 VA 200 mA
PXC Compact 24 24 Vac 20 VA 200 mA
PXC Compact 16 24 Vac 18 VA 200 mA
1)
24 Vdc for up to eight external sensors at 25 mA each. Combined total of the external sensor
power outputs cannot exceed 200 mA ±10% over full operating temperature range.