Fig. 53: Detail of PX Series Enclosure Earth Ground Stud (Under Wire Cover).
Multiple PX Series Service Boxes on One Power Source
The following table shows the number of PX Series Service Boxes allowed on a single
three-wire (ACH, an ACN, and earth ground) circuit, if local code permits.
Number of PX Series Service Boxes Allowed on a Single Three-Wire Circuit.
Maximum Values for
Concentrated Loads
Maximum Values for Evenly
Spaced Loads
Circuit Breaker Size
1
Length
2
192/384 VA
3
Length
2
192/384 VA
3
10 amp (No.14 AWG THHN) (230V models only) 115 ft
(35.06 m)
6/3
130 ft
(40.63 m)
8/4
15 amp (No.14 AWG THHN)
75 ft
(22.87 m)
3/2
100 ft
(30.48 m)
3/2
20 amp (No.12 AWG THHN) 115 ft
(35.06 m)
4/3
130 ft
(40.63 m)
4/3
1)
For 115 Vac versions, assume minimum voltage of 102 Vac at the circuit breaker and 5 Vac maximum voltage drop (97 Vac) at
loads. For 230 Vac versions assume minimum voltage of 204 Vac at the circuit breaker and 10 Vac maximum voltage drop
(194 Vac) at loads. See Class 1 power trunk information in the Wire Specification Tables section of Chapter 1. Smoke control
applications may not exceed 15 ampcircuit breakers.
2)
Conduit length from PX Series Service Box to PX Series Service Box.
3)
Number includes 2A reserved for duplex outlet on 115 Vac versions; not used with 10A circuit breakers.