PX Series Service Boxes
CAUTION
Do not connect inductive loads, such as drill motors, vacuum cleaners, or
compressors, to the duplex receptacle on the 115V Service Box.
PX Series Service Box Source Requirements and Outputs
Maximum Input Maximum 24 Vac Output
PX Series Service Box
Model
Input Voltage Line Frequency Transformer Service
Outlets
Total
1
Class
2
115V 192VA 115 Vac 50/60 Hz 2A 2A
2
192 VA 96 VA
115V 384VA 115 Vac 50/60 Hz 4A 2A
2
384 VA 96 VA
230V 192VA 230 Vac 50/60 Hz 1A N/A 192 VA 96 VA
230V 384VA 230 Vac 50/60 Hz 2A N/A 384 VA 96 VA
1)
Total 24 Vac Output Power is distributed to both Class 1 Power Limited Terminations, for use inside the enclosure only, and a
Class 2 Termination, which may also be used outside the enclosure.
2)
Service outlets (115 Vac only) are not fused or switched, but are restricted to continuously-powered network devices (0.5A) and
reserve power for laptop computers (1.5A). Plan Branch circuit for each additional 2A.
PX Series 115V Service Boxes (192 VA or 384 VA)
DANGER
Possible shock hazard! The power switch only disables power to the control side of
the 24 Vac transformer. Power remains ON at the duplex receptacle (115V versions)
and in the service box. Power may be present at the field devices. To avoid injury,
follow proper safety precautions.
115 Vac source power to the service box enters the enclosure from the top right or
right-hand side conduit knockouts. Source voltage must be current-limited to 20 amps
or less (15 amps or less for Smoke Control), depending on the requirements of the
particular installation.
Two pigtails and an earth grounding stud are provided under the wire cover for easy
connection by an electrician. The AC hot is pre-wired to the transformer through a
single pole On/Off switch and a circuit breaker. The pigtails are also connected to a
duplex receptacle, which is not internally switched or fused. MOVs (3 × 150V) are
installed on input power. Earth ground is available at the CTLR connector and at the
duplex receptacle. Transformer secondary neutral (green) and Service Box earth
ground (green/yellow) have ring terminals for mounting on earth ground stud.