Engineering Documentation

Table Of Contents
Chapter 3 Field Panels
Control Circuit Point Wiring
125
-3002
79 | 231
L2SL (Logical Two State Latched)
WARNING
Do not install the Field Panel HAND/OFF/AUTO (HOA) option for points defined as
L2SL.
NOTE:
DO-1 invert value: NO
DI-2 normally closed: NO
Fig. 47: Connecting an L2SL (Proof Mandatory).
L2SL Control Circuit States.
State DO-1 DI-2
ON ON ON
OFF OFF OFF