Chapter 3 Field Panels
Control Circuit Point Wiring
125
-3002
75 | 231
Chapter 3 Field Panels
Control Circuit Point Wiring
The following illustrations apply to the PXC Modular (TX-I/O), PXC Compact, and
MEC.
LFSSL (Logical FAST/SLOW/STOP Latched)
WARNING
Do not install the Field Panel HAND/OFF/AUTO (HOA) option for points defined as
LFSSL.
NOTE:
DO-1 and DO-2 invert value: NO
DI-3 normally closed: NO
Fig. 43: Connecting an LFSSL (Proof Optional).
LFSSL Control Circuit States.
State DO-1 DO-2 DI-3
FAST ON OFF ON
SLOW OFF ON ON
STOP OFF OFF OFF