Power Trunk Guidelines
66
| 231
125-3002
Fig. 38: Power Trunk Layout, Class 2 Circuits.
CAUTION
Circuits connected to transformers rated over 100 VA must be treated as Class
1, that is, in conduit, separate from ALN, FLN, and point wiring.
When power requirements exceed 100 VA, it is recommended that multiple
transformers 100 VA or less be used, rather than a single transformer.
Fig. 39: Power Trunk Layout, Class 1 Circuit.