Chapter 2 Network Electrical Systems
LONWORKS FLN Communications Wiring
125
-3002
63 | 231
Each network segment (1 without repeater, 3 with repeater) requires a pair of
terminating resistors (part number 587-649, packs of 100) wired in parallel anywhere
on the segment, at the field panel, or at the repeater. See LonWorks FLN Network
Terminations [ 63] in this chapter for more information on segment termination.
Fig. 37: LONWORKS Network Topology
LonWorks FLN Network Terminations
All LonWorks FLN segments must have a single 52 ohm network termination, made
up of two 105 ohm, 1% tolerance, 1/4-watt resistors wired in parallel. These resistors
are available in packages of 100 (P/N 587-649P100).
Recommended Terminator Installation
Install the network terminations as follows:
On a single segment LonWorks FLN, install the termination at the L model MEC.
On a 2 or 3 segment LonWorks FLN, install each segment termination at the
repeater.