Engineering Documentation

Table Of Contents
Chapter 2 Network Electrical Systems
LONWORKS FLN Communications Wiring
125
-3002
61 | 231
Nodes per Subnet/Network
Any device that contains a Neuron ID (and therefore a unique address) is counted as
a node. Devices such as repeaters and network terminators do not have addresses
and thus are not counted as nodes.
Electrical Loads
The number of electrical LonWorks bus loads allowed per segment is 64. All devices,
with the exception of the network terminator, count as one electrical load. Networks
with more than 60 nodes should use a repeater. Two-port (P/N 587-450) and three-
port (P/N 587-455) repeaters are available.
Segment
A LonWorks FLN consists of 1, 2, or 3 network segments. A segment is defined as a
part of the physical network containing nodes that can communicate with each other
without requiring intervention from an intermediate device, such as a repeater.
Wiring Between Buildings
Use a LonWorks repeater for segments that run between buildings to protect the
network against lightning or other high voltage spikes. Additional communication
grade surge suppressors should be used as well.
Repeater Depth
Repeater depth refers to the number of repeaters that can be connected in series to
any given segment. The APOGEE with LonWorks system repeater depth is 1, which
means that only one end of a segment can be connected to a repeater. This allows
you to extend the channel wire length by either one or two segments, depending on
which repeater type you use. Two-port (P/N 587-450) and three-port (P/N 587-455)
repeaters are available.
Network Speeds
The LonWorks FLN operates at 78K bps.
Conduit Sharing
The LON FLN cable can be run in the same conduit or raceway with 24 Vac power
and AI, DI, and AO circuits. For more information on conduit sharing, see Conduit
SharingClass 1/Class 2 Separations [ 14] in this document.
Wire Lengths
The maximum total wire length per segment is calculated by summing the lengths of
all network wire on a segment. The maximum node-to-node length is the maximum
distance allowed between adjacent nodes on the same segment. See Figure
Determining Network LengthExample.
Two-port and three-port repeaters can extend the subnet by providing one or two
additional segments, with wire lengths as defined in Table LonWorks FLN Wiring
Specifications [ 60].