Communication Wiring Requirements
To connect to the LonWorks® network, use 22 AWG twisted pair (TP), level 4,
Echelon® approved wire.
WARNING
Use the recommended LonWorks® cable: 22 AWG unshielded or shielded (where
specified), Level IV per NEMA standards (not equivalent to EIA/TIA Level 4 cable).
Network cabling is not polarity sensitive.
LonWorks FLN Wiring Specifications.
Wire Type and Gauge Max. Total Wire Length (1
Segment)
Max. Node-to-Node
Length
22 AWG 1 pair, stranded, unshielded, level IV per
NEMA standards, blue plenum jacket
1640 ft (500 m) 1312 ft (400 m)
Fig. 35: LonWorks Floor Level Network.