LONWORKS FLN Communications Wiring
125
-3002
59 | 231
LONWORKS FLN Communications Wiring
NOTE:
L model MECs provide a LonWorks® floor level network. Read this section if you are
installing an L model MEC. For F model MECs, see the
P1 FLN section of this
document. Other types of MEC do not provide floor level networks.
Network Requirements
The APOGEE with LonWorks system communicates on a LonWorks compatible Free
Topology floor level network (LonWorks FLN). You must observe the limitations of the
LonTalk® communication protocol (node count, load count, wire specifications, and
wire length limits) when designing the network wiring. Use approved cables only;
these include unshielded and shielded (where specified) two conductor 22 AWG Level
IV cable. See tables in this section, as well as the Table LONWORKS FLN Wiring
Specifications [ 60] and Figure LONWORKS Floor Level Network [ 60].
Logical Network Limitations.
Maximum number of subnets per network 255
Maximum number of nodes per subnet 127
Maximum number of nodes per network 32,385
A system may contain an unlimited number of domains
A node may be a member of two domains
A device may contain more than one node
Physical Network Limitations.
Specification Limit
Maximum electrical bus loads per segment 64
Maximum repeater depth 1
Network terminators (resistors) per segment 2, 105 ohm, wired in parallel
Network speeds 78K bps