Chapter 2 Network Electrical Systems
RS-485 ALN and FLN (P1) Communications Wiring on Structured Cabling
125
-3002
57 | 231
Patch Cables
Field panels and zones are chained with patch cables.
Figure RS-485 ALN and FLN to RJ-45 Chained Patch Cable, 538-908(S) shows a
middle device chain for the field panel or zone.
Figure RS-485 ALN and FLN to RJ-45 Terminated Patch Cable, 538-909(S)
shows a terminated chain for the field panel or Zone.
Figure Multiplexed FLN 1, 2, 3 to RJ-45 Terminated Patch Cable, 538-911(S)
shows three Zones of FLN (P1) multiplexed from a single Field Panel Controller.
Shields (S suffix on part number) are used only where shielded cable is brought to the
field panel or zone, ensuring impedance is maintained. Terminators are used for all
end-of-line connections including both the RS-485 ALN and FLN.
Fig. 32: RS-485 ALN and FLN to RJ-45 Chained Patch Cable, 538-908(S).
Fig. 33: RS-485 ALN and FLN to RJ-45 Terminated Patch Cable, 538-909(S).