Engineering Documentation

Table Of Contents
Chapter 2 Network Electrical Systems
RS-485 MS/TP Communications
44
| 231
125-3002
Before the RS-485 reference terminator is installed, the third wire (yellow) must be
tested with a DMM to insure it is not already connected to earth ground. If the wire is
connected to earth ground the fault condition must be remedied before terminating the
wire using the RS-485 reference terminator.
Fig. 20: Network RS-485 Reference Terminator.
BACnet Nodes on Siemens Controllers or Third-Party
Equipment (Using 1.5 pr cable)
Not all Siemens Building Technologies provide a 3-wire MS/TP network interface. In
order to connect to a 3-wire network use the following diagram as a guide. This guide
may also be used when connecting to third-party controllers that support a 2-wire
interface. If the Master node supports a 3-wire network, then wire the network in the
same manner as the BACnet slaves. The RS-485 common must be referenced to
earth ground through the RS-485 reference terminator (550-974P10) at one end of the
network, (master end preferred).
Depending on the manufacturer, the third wire on 3-wire network interfaces has
several names (for example: Ref, Ground, Com. SC (Signal Common), R (for
Reference), GND, SG (Signal Ground)).
SBT chose the General Ground symbol ( ) as the international symbol for
Equipotential Point versus protective/earth ground or noiseless ground. Some early
BACnet controllers may be marked with the earth symbol ( ) or the S designation.
This pin is not the termination point for the shield of the communications cable.
NOTE:
The symbol ( ), is the symbol being used to represent RS-485 communications
common reference.
Early versions of some controllers may show the earth ground symbol ( ) or the
"S" designation.