Engineering Documentation

Table Of Contents
Chapter 2 Network Electrical Systems
Ethernet Communications Wiring
30
| 231
125-3002
Requirements for Fault Tolerant Star Topology
Ethernet switches must provide one active 10/100BaseTX port for each controller
Maximum cable distance 90m between RJ45 jacks at switch and controller
Switch active port connects to controller upstream port 1
Controller downstream port 2 is not used
Switch ports must be active at time of BACnet/IP commissioning
Controller fault does not impact other controllers
Fig. 8: Star Topology requires one switch port for each controller.
Ethernet Communications Wiring
Preferred Cable Type
Standard TIA/EIA 802.3 (IEEE Std 802.3 or ISO/IEC 8802-3) provides background
material on the basic functioning of the Carrier Sense Multiple Access with Collision
Detection (CSMA/CD) packet network. Wiring guidelines for TIA/EIA 802.3 links are
described in ANSI/TIA/EIA-568-B.1, Commercial Building Telecommunications
Cabling Standard and ANSI/TIA/EIA-606 Cabling Administration.
To minimize risk and reduce installed costs of Ethernet communications wiring, use
the cables listed in the following table for all estimates and installations.
Preferred Cable Type.
Equipment Connection
Requirements
Basic Link * Patch Cable* Jacks and Patch Panels
MLN
ALNs:
Ethernet
BACnet/IP
AEM
Hubs
Switches
Routers
Network Interface
Card
10Base-T
(10 Mbps)
IEEE 802.3 Category 3 certified solid
cable or better, terminated in the
field panel or at the computer with a
standard RJ-45 jack.
IEEE 802.3 Category 3
certified stranded cable or
better.
IEEE 802.3 Category 3
certified RJ-45 connectors
or better.
100Base-TX
(100 Mbps)
IEEE 802.3 Category 5e certified
solid cable or better, terminated in
the field panel or at the computer
with a standard RJ-45 jack.
IEEE 802.3 Category 5e
certified stranded cable or
better.
IEEE 802.3 Category 5e
certified RJ-45 connectors
or better.
*See Wire Specification Tables [
24] in Chapter 1.