Engineering Documentation

Table Of Contents
Chapter 1 Wiring Regulations and Specifications
Wire Specification Tables
26
| 231
125-3002
Punch Down Block Jumper Cable.
Cable configuration 1 Unshielded Twisted Pair (UTP), no jacket
Gauge 24 AWG (solid)
IEEE 802.3 Category 5e or better
UL type CM, CMP, CMR (75°C or higher)
CSA type FT4, FT6 (75°C or higher)
LON Networking Wiring.
Cable configuration Unshielded or shielded pair
Gauge 22 AWG (stranded)
Capacitance 17 pf/foot @ 1 KHz, 1 MHz
UL type CM, CMP, CMR (75°C or higher)
CSA type FT4, FT6 (75°C or higher)
TX-I/O Island Bus Wiring.
1)
Cable configuration
1 Twisted Shielded Pair (TSP) + 1 Twisted Shielded
3C (Triad)
-or- 1 Twisted Shielded 4C
-or- 2 Twisted Pair (TP)
Gauge 14 or 16 AWG (stranded)
Capacitance 54 pf/ft or less
Twists per foot 3 to 4
Shields 100% foil with drain wire (except TP)
NEC class UL listed, CM, CMP (75°C or higher)
CEC class FT4, FT6 (75°C or higher)
1)
See TX-I/O Island Bus Guidelines [
91] in Chapter 3 for cable configuration.
KNX/PL-Link Signal and Power Cable.
Cable configuration 1 Twisted Shielded Pair (1 TSP)
Gauge No. 18 to 20 AWG (solid BC)
Capacitance 32pf/ft, (70pf/ft 18 AWG)
Twists per foot 3 to 4
Shields 100% foil with drain wire (do not connect drain wire
to earth ground).
NEC class UL listed, CMP (300 Vac, 75°C or higher)
CEC class FT6, (300 Vac, 75°C or higher)