Engineering Documentation

Table Of Contents
Chapter 1 Wiring Regulations and Specifications
Wire Specification Tables
125
-3002
25 | 231
Class 2 for Point Usage Only (in Conduit and per Local Codes).
1)
Cable configuration Twisted pair (unjacketed) or TSP
Gauge No. 18 to No. 22 AWG (stranded)
Capacitance N/A
Twists per foot 4 minimum
Shields Not required (in case of TSP, 100% foil with drain
wire)
UL (CSA) listed voltage rating 300 Vac
UL (CSA) listed temperature rating 75°C (167°F) or higher
1)
300 Vac wire can be used in field panels containing voltages below 150 Vac.
Class 2 for Low-Voltage Applications Only (Except Trunk).
Cable configuration Twisted pair or Twisted shielded pair (TSP)
Gauge No. 18 to No. 22 AWG (stranded)
Capacitance N/A
Twists per foot 4 minimum
Shields Not required (in case of TSP, 100% foil with drain
wire)
UL type CM, CMP, CMR (75°C or higher)
CSA type FT4, FT6 (75°C or higher)
Ethernet Basic Link.
Cable configuration 4 Unshielded Twisted Pair (UTP)
Gauge 24 AWG (solid)
Capacitance 17 pf/foot @ 1 KHz, 1 MHz
IEEE 802.3 Category 5e or better
Shields Optional where required
UL type CM, CMP, CMR (75°C or higher)
CSA type FT4, FT6 (75°C or higher)
Ethernet Patch Cable.
Cable configuration 2 or 4 Unshielded Twisted Pair (UTP)
Gauge 24 AWG (stranded)
IEEE 802.3 Category 5e or better
UL type CM, CMP, CMR (75°C or higher)
CSA type FT4, FT6 (75°C or higher)