Engineering Documentation

Table Of Contents
Chapter 1 Wiring Regulations and Specifications
Wire Specification Tables
24
| 231
125-3002
Wire Specification Tables
NOTE:
Wire that meets these specifications can be ordered from the Field Purchasing Guide
under Siemens Industry corporate pricing agreements.
ALN, FLN, and TX-I/O IBE 3-Wire Cable.
1)
Cable configuration 1.5-Pair (1 TP & 1 Conductor) w/overall Shield and
drain wire
Gauge 24 AWG (stranded)
Capacitance 12.5 pf/foot or less
Twists per foot 4 minimum
Shields 100% foil with drain wire
NEC class UL listed, CM, CMP (75°C or higher)
CEC class FT4, FT6 (75°C or higher)
1)
Required for ALN, FLN, and BACnet MS/TP networks that use the new 3-wire interface, ( - +);
preferred for TX-I/O island bus expansion. For PXC Compact, PXC Modular, P1 BIM, and BACnet
equipment controllers, use the Network Wiring Requirements Decision Tree [ 35] in Chapter 2 to
determine if 1.5-pair or 1-pair cable should be used.
ALN, FLN (P1), Point Expansion Trunk, and TX-I/O IBE.
1)
Cable configuration Twisted shielded pair (TSP)
Gauge 24 AWG (stranded)
Capacitance 12.5 pf/foot or less
Twists per foot 4 minimum
Shields 100% foil with drain wire
NEC class UL listed, CM, CMP (75°C or higher)
CEC class FT4, FT6 (75°C or higher)
1)
For use with older 2 -wire networked products. (TEC, SCU, MEC, PXM, MBC). May be used for
TX-I/O island bus expansion.
Class 1 Power Trunk.
1)
Cable configuration 3 conductor
Gauge 12 AWG or 14 AWG THHN
UL type THHN
1)
Circuit breaker sizes: 20 amp for 12 AWG THHN and 15 amp for 14 AWG THHN. Assumes
minimum voltage of 102 Vac at circuit breaker and 5 Vac maximum voltage drop (97 Vac at loads).
Class 2 Power Trunk.
Cable configuration 2 conductor
Gauge 14 AWG, 16 AWG, 18 AWG, 20 AWG
UL type CL2, CL2R, CL2P
CSA type FT4, FT6