Wiring DI Common (pin 4) t 10K/100K selectable thermistor 8 Vdc (pin 2)
incorrectly, will cause the actuator to shut down. No damage will occur. When the
wiring is corrected, the actuator will resume operation.
Digital Output (DO) Wiring
The Wire Type Requirements [ 217] provides DO wire run lengths for points wired to
TECs.
UL and CSA listing requires the DO wiring shield be installed in the cabinets for which
they are supplied.
NOTE:
See the Installation Instructions for point wiring diagrams.
Terminal Equipment Controllers - Pneumatic Output
Do not control more than the nameplate rated loads for the DOs of the pneumatic
output controllers. The controller UL and CSA listing is based on the nameplate power
rating.
The Terminal Equipment Controller Pneumatic Output controls 24 Vac loads only.
The maximum rating is 12 VA for each DO. For higher VA requirements, 110 or 220
Vac requirements, separate transformers used to power the load, or DC power
requirements, use an interposing 220 V 4-relay module (TEC Relay Module P/N 540-