Engineering Documentation

Table Of Contents
Appendix A Discontinued Products
Terminal Equipment Controllers (APOGEE Legacy Controllers)
218
| 231
125-3002
CAUTION
The neutral side of the 24 Vac power transformer for the TEC must be tied to earth
at the source of the 24 Vac and only at this point.
N Variant TEC (Updated Hardware) Power Source Requirements.
Product Input Voltage Line Frequency Maximum Power
1
Terminal Equipment
Controller—Electronic Output
(6 DO Platform)
24 Vac 50/60 Hz 3 VA
+ 12 VA max per DO
Terminal Equipment
Controller—Electronic Output
(8 DO Platform)
24 Vac 50/60 Hz
7 VA
+ 12 VA max per DO
TEC (Legacy Hardware) Power Source Requirements.
Product Input Voltage Line Frequency Maximum Power
1
Terminal Equipment
Controller—Electronic Output
(6 DO Platform)
24 Vac 50/60 Hz 10 VA
+ 12 VA max per DO
Terminal Equipment
Controller—Electronic Output
(8 DO Platform)
24 Vac 50/60 Hz 10 VA
+ 12 VA max per DO
1)
Total VA rating is dependent upon the controlled DO loads (for example, actuators, contactors, etc.).
2)
Smoke control listed TECs are limited to 6 VA max per DO.