TCU Power Source Requirements.
Product Input Voltage Line Frequency Maximum Power
TCU 24 Vac 50/60 Hz 14 – 22.7 VA
1
1)
Dependent on application.
Digital Output (DO) Wiring
Table MPU and DPU Wire Requirements provides DO wire run lengths for points
wired to Terminal Control Units.
UL and CSA listing requires the DO wiring shield be installed in the cabinets for which
they are supplied.
Grounding
A ground lug is provided on TCUs, if required due to local codes or for RF grounding
reasons.
Metal Oxide Varistors (MOVs)
Metal Oxide Varistors (MOVs) must be used across the DO terminals when connected
to loads. MOVs are factory-installed in all FLN products.
When installing MOVs across the DO relay contacts on termination boards, keeping
the MOV leads as short as possible makes the MOV more effective at reducing spikes
from field wiring or controlled devices. Remove and reinstall any MOVs with leads
longer than 1 in. (2.5 cm). See the section Controlling Transients [ 23] for MOV part
numbers.
Line Voltage Relay Module
Low voltage MOVs can be required if severe noise problems arise. A jumper is
provided to allow you to position the snubber across either the normally open (NO) or
normally closed (NC) contacts.
Unitary Controller (UC)
NOTE:
The Unitary Controller (UC) is no longer available for new sales. Information in this
section is for reference only.