Engineering Documentation

Table Of Contents
Appendix A Discontinued Products
Terminal Equipment ControllerPneumatic Output, Low Voltage
125
-3002
213 | 231
Fig. 169: Locally-powered Actuator Connection to the LTEC.
Remotely-powered Actuator Connections
Remote actuators, where the actuator and the LTEC are served by separate
transformers, can be wired to LTEC outputs AO 1, AO 2, or AO 3 on terminal block J7
(Figure Remotely-powered Actuator Connection to the LTEC).
NOTE:
Figure Remotely-powered Actuator Connection to the LTEC illustrates the actuator
connecting to output terminals J7-3 and J7-4, which correspond to termination set
AO 2.
Fig. 170: Remotely-powered Actuator Connection to the LTEC.
Analog Output (0-10 Vdc) Wiring Details.
Termination Set Terminal Numbers
Signal Out Common
AO 1* J7-1 J7-2
AO 2* J7-3 J7-4
AO 3*
(only available on Unit Ventilator
controllers)
J7-5 J7-6
*
Available on full point controller only.