Engineering Documentation

Table Of Contents
Appendix A – Discontinued Products
Terminal Equipment ControllerPneumatic Output, Low Voltage
212
| 231
125-3002
Lighting Contactor—Pulsed Wiring Details.
Termination Set Terminal Numbers
Triac Control Output 24V Sources
DO 1 J3-1 J3-2
DO 2 J3-3 J3-4
DO 3 J3-5 J3-6
DO 4 J3-7 J3-8
DO 5 J3-9 J3-10
DO 6 J3-11 J3-12
DO 7* J3-13 J3-14
DO 8* J3-15 J3-16
*
Available on full point controller only.
Analog Output (0-10 Vdc)
An analog output (0-10 Vdc) can be wired to the LTEC outputs AO 1 or AO 2 on all
controllers and to AO 1 through AO 3 on Unit Ventilator Controllers. Use terminal
block J7 (Figure Analog Output (0-10 Vdc) Connection to the LTEC).
NOTE:
Figure Analog Output (0-10 Vdc) Connection to the LTEC illustrates an analog output
(0-10 Vdc) connecting to output terminals J7-3 and J7-4, which correspond to
termination set AO 2.
Fig. 168: Analog Output (0-10 Vdc) Connection to the LTEC.
Locally-powered Actuator Connections
Local actuators, where the actuator and the LTEC share one transformer, can be
wired to LTEC outputs AO 1, AO 2, or AO 3 on terminal block J7 (Figure Locally-
powered Actuator Connection to the LTEC).
NOTE:
Figure Locally-powered Actuator Connection to the LTEC illustrates the actuator
connecting to output terminals J7-3 and J7-4, which correspond to termination set
AO 2.