Appendix A Discontinued Products
Terminal Equipment ControllerPneumatic Output, Low Voltage
210
| 231
125-3002
Digital Output3 Position Floating Motor Wiring Details.
Termination Set Terminal Numbers
Triac Control Output 24V Sources
DO 1 J3-1 J3-2
DO 2 J3-3 J3-4
DO 3 J3-5 J3-6
DO 4 J3-7 J3-8
DO 5 J3-9 J3-10
DO 6 J3-11 J3-12
DO 7* J3-13 J3-14
DO 8* J3-15 J3-16
*
Available on full point controller only.
Lighting ContactorMaintained
A single lighting contactor or interface relay, or a single point that drives multiple
lighting contactors can be wired to the LTEC outputs DO 1 through DO 8 on terminal
block J3.
NOTE:
Figure Lighting ContractorMaintained Connection to the LTEC illustrates a lighting
contactor or interface relay connecting to output terminals J3-15 and J3-16, which
correspond to termination set DO 8.
Fig. 166: Lighting Contactor—Maintained Connection to the LTEC.