Engineering Documentation

Table Of Contents
Chapter 1 Wiring Regulations and Specifications
Conduit Fill
125
-3002
21 | 231
Nominal Conduit Fill—NEC Requirements.
Insulated
Conductor
Conduit I.D. Area Quantity in Conduit
2)
O.D. (inches)
1)
Conductor Area
(sq. in.)
1/2“ EMT
0.622
0.304
3/4“ EMT
0.824
0.533
1“ EMT
1.049
0.864
1-1/4" EMT
1.380
1.496
1-1/2" EMT
1.610
2.036
2" EMT
2.067
3.356
0.400 0.126 1 1 2 5 6 10
0.390 0.119 1 1 3 5 7 11
0.380 0.113 1 1 3 5 7 12
0.370 0.108 1 1 3 5 7 12
0.360 0.102 1 1 3 6 8 13
0.350 0.096 1 1 3 6 8 14
0.340 0.091 1 2 4 6 9 15
0.330 0.086 1 2 4 7 9 15
0.320 0.080 1 2 4 7 10 16
0.310 0.075 1 3 4 8 11 18
0.300 0.071 1 3 5 8 11 19
0.295 0.068 1 3 5 8 12 19
0.290 0.066 1 3 5 9 12 20
0.285 0.064 1 3 5 9 13 21
0.280 0.062 1 3 5 9 13 22
0.275 0.059 1 3 6 10 13 22
0.265 0.055 1 4 6 11 15 24
0.255 0.051 2 4 7 11 16 26
0.245 0.047 2 4 7 12 17 28
0.235 0.043 3 5 8 14 19 31
0.225 0.040 3 5 8 15 20 33
0.215 0.036 3 6 9 16 22 37
0.205 0.033 3 6 10 18 24 40
0.195 0.030 4 7 11 20 27 45
0.185 0.027 4 8 13 22 30 50
0.175 0.024 5 9 14 25 34 56
0.165 0.021 5 10 16 28 38 63
0.155 0.019 6 11 18 31 43 71
0.145 0.017 7 13 21 36 49 81
0.135 0.014 8 15 24 42 57 94
0.125 0.012 10 17 28 48 66 109
0.115 0.010 11 20 33 57 78 129
0.105 0.009 14 24 40 69 94 155