Terminal Equipment ControllerPneumatic Output, Low Voltage
125
-3002
209 | 231
Digital OutputON/OFF Wiring Details.
Termination Set Terminal Numbers
Triac Control Output 24V Sources
DO 1 J3-1 J3-2
DO 2 J3-3 J3-4
DO 3 J3-5 J3-6
DO 4 J3-7 J3-8
DO 5 J3-9 J3-10
DO 6 J3-11 J3-12
DO 7* J3-13 J3-14
DO 8* J3-15 J3-16
*
Available on full point controller only.
3-Position Floating Motor
A 3-position floating motor can be wired to two sets of consecutive terminations on the
LTEC outputs DO 1 through DO 8. Use terminal block J3.
NOTE:
Figure 3-Position Floating Motor Connection to the LTEC illustrates a 3-position
floating motor connecting to output terminals J3-1, J3-2, J3-3, and J3-4, which
correspond to termination set DO 1 and DO 2.
Fig. 165: 3-Position Floating Motor Connection to the LTEC.
NOTE:
The outputs of the 3-position floating motor must be wired across two sets of
consecutive terminal blocks (that is, DO 1 to DO 2, DO 2 to DO 3, DO 3 to DO 4,
etc.).