Engineering Documentation

Table Of Contents
Appendix A Discontinued Products
Terminal Equipment ControllerPneumatic Output, Low Voltage
208
| 231
125-3002
Analog Input (Current) Wiring Details.
Termination Set Terminal Numbers Internal Jumper
Signal
+
Common
AI 3/DI 3 J4-1 J4-2
AI 4/DI 4 J4-3 J4-4
AI 5/DI 5* J4-6 J4-7 N/A1
1)
Use external 499Ω 1% resistor across terminal 6-7.
*
Available on full point controller only.
Digital OutputON/OFF
ON/OFF digital outputs can be wired to the LTEC outputs DO1 through DO 8 on
terminal block J3.
NOTE:
Figure Digital Output (ON/OFF) Connection to the LTEC illustrates an ON/OFF d
igital
output connecting to output terminals J3-1 and J3-2, which correspond to termination
set DO 1.
Fig. 164: Digital Output (ON/OFF) Connection to the LTEC.