Engineering Documentation

Table Of Contents
Appendix A Discontinued Products
Terminal Equipment ControllerPneumatic Output, Low Voltage
125
-3002
207 | 231
Analog Input (Voltage) Wiring Details.
Termination Set Terminal Numbers Internal Jumper
Signal
+
Common
AI 3/DI 3 J4-1 J4-2
AI 4/DI4 J4-3 J4-4
AI 5/DI 5* J4-6 J4-7 N/A
*
Available on full point controller only.
Analog Input (Current)
Analog inputs (4-20 mA current) can be wired to the LTEC inputs AI 3/DI 3 through AI
5/DI 5 on terminal block J4. For AI 3/DI 3 and AI 4/DI 4, use the internal jumper block
for current input as shown in Figure 136. For AI 5/DI 5, use an external resistor as
shown in Figure 137.
NOTE:
Figure 136 illustrates an analog input (current) connecting to input terminals J4-
1 and
J4-2, which correspond to termination set AI 3/DI 3.
Figure 136. Analog Input (Current) Connection to
LTEC Input AI3/DI3 or AI 4/DI 4.
Figure 137. Analog Input (Current) Connection to
LTEC Input AI 5/DI 5.