Engineering Documentation

Table Of Contents
Appendix A Discontinued Products
Terminal Equipment ControllerPneumatic Output, Low Voltage
206
| 231
125-3002
NOTE:
Figure Digital Input Connection to LTEC Inputs AI 1/DI 1, AI 2/DI 2, or AI 5/DI 5
illustrates a digital input connecting to input terminals J6-2 and J6-3, which
correspond to termination set AI 1/DI 1. Figure Digital Input Connection to LTEC
Inputs AI 3/DI 3 or AI 4/DI 4 illustrates a digital input connecting to input terminals J4-
1 and J4-2, which correspond to termination set AI 3/DI 3.
Digital Input Wiring Details.
Termination
Set
Terminal Number Internal Jumper
DI (Voltage Source)
+5
Signal
+
Common
AI1/DI1 J6-1 J6-2 J6-3 N/A
AI2/DI2 J6-4 J6-5 J6-6 N/A
AI3/DI3 N/A J4-1 J4-2
AI4/DI4 N/A J4-3 J4-4
AI5/DI5* J4-5 J4-6 J4-7 N/A
*
Available on full point controller only.
Analog Input (Voltage)
Analog inputs (voltage) can be wired to the LTEC inputs AI 3/DI 3 through AI 5/DI 5 on
terminal block J4 (Figure 134). For AI 5/DI 5, connect directly to J4-6 and J4-7; no
jumpers are required (Figure 135).
NOTE:
Figure 134 illustrates an analog input (voltage) connecting to input terminals J4-1
and J4-2, which correspond to termination set AI 3/DI 3.
Figure 134. Analog Input (Voltage) Connection to
LTEC Inputs AI 3/DI 3 and AI 4/DI 4.
Figure 135. Analog Input (Voltage) Connection to
LTEC Input AI 5/DI 5.