Engineering Documentation

Table Of Contents
Appendix A Discontinued Products
Terminal Equipment ControllerPneumatic Output, Low Voltage
125
-3002
205 | 231
NOTE:
Figure 132 illustrates a digital input connecting to input terminals J6-2 and J6-3,
which correspond to termination set AI 1/DI 1. Figure 133 illustrates a digital input
connecting to input terminals J4-1 and J4-2, which correspond to termination set AI
3/DI 3.
Digital Input Wiring Details.
Termination
Set
Terminal Numbers Internal Jumper
DI (Voltage Source)
+5
Signal
+
Common
AI 1/DI 1 J6-1 J6-2 J6-3 N/A
AI 2/DI 2 J6-4 J6-5 J6-6 N/A
AI 3/DI 3 N/A J4-1 J4-2
AI 4/DI 4 N/A J4-3 J4-4
AI 5/DI 5* J4-5 J4-6 J4-7 N/A
*
Available on full point controller only.
AI 1/DI 1, AI 2/DI 2, or AI 5/DI 5
Digital inputs can be wired to the LTEC inputs AI 1/DI 1, AI 2/DI 2, or AI 5/DI 5 on
terminal block J4 or J6. An external jumper provides a 5 Vdc source to be used for
sensing dry contacts.
AI 3/DI 3 or AI 4/DI 4
Digital inputs can be wired to the LTEC inputs AI 3/DI 3 or AI 4/DI 4 on terminal block
J6 (Figure Digital Input Connection to LTEC Inputs AI 3/DI 3 or AI 4/DI 4). For these
inputs, use the internal jumper blocks, J12 and J13 respectively, and configure them
as shown in Table Digital Input Wiring Details.
Digital Input Connection to LTEC Inputs AI 1/DI 1,
AI 2/DI 2, or AI 5/DI 5.
Digital Input Connection to LTEC Inputs AI 3/DI 3
or AI 4/DI 4.