Engineering Documentation

Table Of Contents
Appendix A Discontinued Products
Terminal Equipment ControllerPneumatic Output, Low Voltage
200
| 231
125-3002
Load Limits
Allowable loads for the LTEC are 24 Vac devices (actuators, interposing relays, motor
contactor control coils, solenoids, lamps or indicators) rated at 12 VA or less for each
termination set. If the load exceeds 12 VA @ 24 Vac, an interposing relay must be
used.
CAUTION
The entire digital output load on a single LTEC must not exceed 95 VA.
Power for the loads is obtained from the same terminals that supply power to the
LTEC. If fusing is required, 3/4 amp slow blow fuses are recommended per digital
output. The entire LTEC and its loads must be powered from a 24 Vac line fused at 4
amps (100 VA) or less.
NOTE:
The LTEC uses triacs to control digital output loads. The triacs are rated at 500 mA
at 24 Vac for a power rating of 12 VA for each termination set.
LTEC Wiring Diagrams
Each application set has a default input/output-wiring configuration shown in the wiring
diagrams. All input and output physical connections are pre-configured per application.
See the installation instructions for application-specific wiring diagrams.
The wiring diagrams are shown using the full point controllers (shaded terminals).
Reduced point controllers should be used when the additional input/output points are
not required.
Points shown as optional on the wiring diagrams are pre-configured I/O points. In
some instances, some configuration parameters will need to be modified to use these
points.