LTEC Inputs and Outputs.
Specification Details
Application inputs 100K Ω thermistor/0 to 10 Vdc, 4 to 20 mA, or dry contact
Room sensor input 10K Ω thermistor
Digital outputs Triac (max. 500 mA at 24 Vac)
Analog outputs 0 to 10 Vdc (max. 12.5 mA)
LTEC Room Temperature Sensor Specifications.
Specification Details
Resistance value (sensor) 10K Ω thermistor @ 77°F (25°C)
Output signals
• Room temperature
• Set point
• Occupancy (bypass button)
• Changing resistance
• Changing resistance
• Digital
Installation 100 ft (30.5 m) maximum cable length
3 pr. 24 AWG, NEC Class 2
Power Source Requirements
Transformer Requirements and Recommended Voltages
The base rating of the controller and the sum of the sensor, actuators, and relays
connected dictates the VA rating.
CAUTION
The LTEC Digital Outputs (DOs) control 24 Vac only. The maximum rating is
12 VA for each DO. Use an interposing 24 Vac relay for any of the following:
- VA requirements higher than the maximum
- 110 to 220 Vac or higher
- Control load requires DC power
- Separate transformers used to power the load
- Need for dry contacts
CAUTION
The neutral side of the 24 Vac power transformer for the TEC must be tied to earth
at the source of the 24 Vac and only at this point.
LTEC Power Source Requirements.
Product Input Voltage Line Frequency Maximum Power
LTEC 24 Vac 50/60 Hz 5 VA plus loads