Terminal Equipment ControllerPneumatic Output, Low Voltage
125
-3002
197 | 231
Terminal Equipment Controller—Pneumatic
Output, Low Voltage
NOTE:
The Pneumatic TEC is no longer available for new sales. Information in this section
is for reference only.
When placing the low voltage, (24 Vac Class 2), pneumatic output Terminal
Equipment Controllers on a power trunk, use the nameplate power rating for
calculating the maximum number of devices that can be placed on a Class 2 power
trunk. The nameplate power rating takes into account a controller power factor of less
than unity.
Terminal Equipment ControllersPneumatic Output
Do not control more than the nameplate rated loads for the DOs of the pneumatic
output controllers. The controller UL and CSA listing is based on the nameplate power
rating.
The separate FAN output (Form A dry contact) on the Unit Vent Controllers is rated at
1/3 H.P. at 115 or at 230 Vac. The digital output, which is part of the large wiring
harness, switches the incoming power to the controller. This cable can contain up to
230 Vac depending on controller input voltage. The 115 and 230 Vac controllers use a
molded cord for this output. Exceeding the nameplate power on this output can
damage the controller circuit board.
Pneumatic Output Controller
The power source for the high voltage Unit Vent Controller should be obtained after
the fuse in the unit ventilator. By obtaining the power for the controller after the fuse,
you can ensure that the controller is powered down whenever the fuse opens or is
removed.
TEC Power Source Requirements.
Product Input Voltage Line Frequency Maximum Power
Terminal Equipment Controller—
Pneumatic Output, Low Voltage
24 Vac
50/60 Hz 12 VA
+ damper output
Terminal Equipment Controller—
Pneumatic Output, High Voltage
115 Vac 50/60 Hz 7 VA
+ damper output
Terminal Equipment Controller—
Pneumatic Output, High Voltage
230 Vac 50/60 Hz
7 VA
+ damper output
1)
Service outlets are restricted to only continuously power network devices.
Pneumatic Output Wire Type Requirements.
Circuit Type Class Wire Type (AWG) Distance
2
Conduit Sharing
1
Input Power
(Low voltage controllers)
2 Check local codes Check local codes Check local codes
Input Power (Unit Vent
Controller—115/230V)
1 Check local codes Check local codes Check local codes
Damper Output