Digital Outputs
SCUs with Rev. 7 or earlier termination boards do not contain factory-installed MOVs.
These must be field installed.
SCUs with Revisions 8 through 16 termination boards have one MOV installed across
the NO contacts. One additional MOV is required when using the normally closed
(NC) contacts.
SCUs with Rev. 17 or later termination boards have two MOVs installed per point. No
additional MOVs are required.
Fig. 154: Field Installed MOVs.
Network Devices
NOTE:
The TI and IPMDA are no longer available for new sales. Information in this section
is for reference only.
Power Source Requirements.
Product
Input Voltage
Line Frequency
Maximum Power
TI 115/230 Vac 50/60 Hz 10 VA
IPMDA 115/230 Vac 50/60 Hz 25 VA
Multi-Point Unit/Digital Point Unit (MPU/DPU)
NOTE:
The DPU and MPU are no longer available for new sales. Information in this section
is for reference only.