Point Wiring Restrictions
Wire specified in the BLN, FLN (P1), and Point Expansion Trunk table in Chapter 1
can be used at any trunk speed.
Metal Oxide Varistors (MOVs)
Line Voltage Receptacle
MOVs are factory-installed on all FLN Controller receptacles.
Stand-alone Control Unit (SCU)
NOTE:
The SCU is no longer available for new sales. Information in this section is for
reference only.
Wire Type Requirements
SCU Wire Type Requirements.
Circuit Type Class Wire Type Distance Conduit Sharing
1
AC Line Power Power No.12 to No.14 THHN See NEC Check local codes
Digital Output 1, 2 Check local codes Check local codes Check local codes
Digital Input 2
No.18 to No.22 TP 2
CL2, CL2P, CM (FT4), or CMP (FT6)
750 ft
(230 m)
Class 1 and 2
(Check local codes)
Analog Input
(4 to 10 mA, Thermistor,
Voltage)
2 No.18 to No.22 TP 2
CL2, CL2P, CM (FT4), or CMP (FT6)
750 ft
(230 m)
Class 2 only
Analog Output
(4 to 10 mA or Voltage)
2
No.18 to No.22 TP 2
CL2, CL2P, CM (FT4), or CMP (FT6)
750 ft
(230 m)
Class 2 only
1)
Conduit sharing rules: No Class 2 point wiring can share conduit with any Class 1 wiring except as noted for Digital Inputs and
where local codes permit.
2)
Twisted pair, non-jacketed, rated 75°C and 300V cable can be used in place of CL2, CL2P, CM (FT4), or CMP (FT6) cable
when contained in conduit per local codes. Both CM and CMP must be rated 75°C or higher. See the Field Purchasing Guide
for
wire.
NOTE:
UL-recognized wire (labeled with a backwards “RU”) is not field-installable. Use only
UL-listed wire.