Fig. 151: Connecting an L2SP (Proof of Voltage).
FLN Controller
Wire Type Requirements
FLN Controller Wire Type Requirements.
Circuit Type Class Wire Type Distance Conduit Sharing
1
AC Line Power Power No. 12 to No. 14 THHN See NEC Check local codes
1)
Conduit sharing rules: No Class 2 point wiring can share conduit with any Class 1 wiring except
as noted for Digital Inputs where local codes permit.
NOTE:
UL-recognized wire (labeled with a backwards “RU”) is not field-installable. Use only
UL-listed wire.
Power Source Requirements
Power Source Requirements for FLN Controller.
Product Input Voltage Line Frequency Maximum
Power
FLN Controller – 115V 115 Vac 50/60 Hz 12 VA
1
FLN Controller – 230V 230 Vac 50/60 Hz 12 VA
1
1)
Service outlets are restricted to continuously power network devices only.